引用本文:葛亮,谭志海,赵凤青,等.一种改进型馈线自愈控制方案及实现[J].电力系统保护与控制,2013,41(18):61-67.
GE Liang,TAN Zhi-hai,ZHAO Feng-qing,et al.An improved feeder self-healing control scheme and its realization[J].Power System Protection and Control,2013,41(18):61-67
【打印本页】   【下载PDF全文】   查看/发表评论  【EndNote】   【RefMan】   【BibTex】
←前一篇|后一篇→ 过刊浏览    高级检索
本文已被:浏览 4783次   下载 272 本文二维码信息
码上扫一扫!
分享到: 微信 更多
一种改进型馈线自愈控制方案及实现
葛亮1, 谭志海1, 赵凤青1, 翁磊1, 董旭柱2
1.北京四方继保自动化股份有限公司,北京 100085;2. 南方电网科学研究院有限责任公司,广东 广州 510080
摘要:
对主干线的分布式和集中型自愈控制方案,分别介绍了其处理逻辑流程,总结了各自的优点、缺点。针对主干线分布式和集中型自愈控制方案的优缺点,考虑IEC61850在自愈控制方案中的应用,提出了一种改进型自愈控制方案。该方案对于故障诊断、定位和隔离采用和分布式自愈控制相同的逻辑流程,对存在多恢复方案的故障下游失电负荷的供电恢复采用执行故障处理预案的方式。故障处理预案在主站事先定义好,并通过IEC61850通信规约下发到相应的智能配网终端,由智能配网终端在故障恢复时判断当前电网状态后执行相应的故障处理预案,实现故障下游负荷的供电恢复。该改进型自愈控制方案集中了分布式和集中型自愈控制方案的优点,同时避免了其缺点和不足之处。理论分析和工程应用表明,提出的改进型自愈控制方案具有较强的工程实用性。
关键词:  配电自动化  馈线自愈控制  分布式  集中型  IEC61850
DOI:10.7667/j.issn.1674-3415.2013.18.010
分类号:
基金项目:国家高技术研究发展计划(863计划)课题14 (2011AA05A114)
An improved feeder self-healing control scheme and its realization
GE Liang,TAN Zhi-hai,ZHAO Feng-qing,et al
Abstract:
The logic processing course of both distributed mode and centralized mode for trunk line is introduced, and the advantages and shortcomings of two modes are also summarized. Because of the advantages and shortcomings of two modes for trunk line, an improved self-healing control scheme is presented and the use of IEC61850 standard for feeders self-healing application is taken into account. This scheme adopts the same logic processing course of fault diagnosis, fault location and fault isolation as the distributed mode. For the load in the offside of fault location, which has multiple power supply restoration ways, the method of implementing the defined plans is used for the fault processing procedure. Fault processing plans are defined in the master station in advance, and they are transmitted to the appropriate intelligent distribution terminal unit by IEC61850 communication protocol. During power supply restoration the intelligent distribution terminal unit performs the appropriate fault processing plan to restore the power supply for the load in the offside after it determines the current state of power grid. The improved self-healing control scheme possesses the advantages of both distributed mode and centralized mode, while avoiding their weaknesses. Theoretical analysis and engineering application indicate that improved self-healing control scheme presented has strong practicality in engineering.
Key words:  distribution automation  feeder self-healing control  distributed mode  centralized mode  IEC61850