引用本文:李晓波,苗晓鹏,桑振华,等.基于偏置阻抗法的配电网电容电流测量新方法[J].电力系统保护与控制,2014,42(4):22-26.
LI Xiao-bo,MIAO Xiao-peng,SANG Zhen-hua,et al.A new capacitive current measurement method of the distribution network based on bias impedance[J].Power System Protection and Control,2014,42(4):22-26
【打印本页】   【下载PDF全文】   查看/发表评论  【EndNote】   【RefMan】   【BibTex】
←前一篇|后一篇→ 过刊浏览    高级检索
本文已被:浏览 5632次   下载 2925 本文二维码信息
码上扫一扫!
分享到: 微信 更多
基于偏置阻抗法的配电网电容电流测量新方法
李晓波1, 苗晓鹏1, 桑振华1, 蔡旭2
1.中国矿业大学信息与电气工程学院,江苏 徐州 221116;2.上海交通大学电子信息与电气工程学院,上海 200240
摘要:
分析了目前配电网电容电流测量方法所存在的问题,提出了一种偏置阻抗法测量电容电流的新方法。该方法通过在配电网中任意一相与地之间串入一固定电阻和可调电抗,调节电抗器,同时观察和测量中性点电压与偏置相对地电压的相角差,来配合电抗器的进一步调节,当该相角差接近90°时,即可精确地测量出电网对地参数。通过Matlab仿真和理论计算得到了一致的结果,同时验证了该方法能够取得比较精确的测量效果。该方法具有操作简单,测量精度高,不会引起中性点过电压等优点,可以应用于配电网电容电流的测量。
关键词:  配电网  偏置阻抗法  相角差  对地参数  测量效果
DOI:10.7667/j.issn.1674-3415.2014.04.004
分类号:
基金项目:国家自然科学基金(51107143)
A new capacitive current measurement method of the distribution network based on bias impedance
LI Xiao-bo1, MIAO Xiao-peng1, SANG Zhen-hua1, CAI Xu2
1.School of Information and Electrical Engineering, China University of Mining and Technology, Xuzhou 221116, China;2.School of Electronic Information and Electrical Engineering, Shanghai Jiao Tong University, Shanghai 200240, China
Abstract:
A new capacitive current measurement method of the distribution network is proposed based on the analysis of the problems existed in the current capacitive current measurement methods. First, a fixed resistance and an adjustable inductor are installed in series between any one phase and the ground; second, the adjustable inductor is regulated, and at the same time, the phase angle difference between the neutral voltage and the bias phase voltage is observed; then the system ground capacitance and resistance can be calculated when the phase angle difference mentioned above is close to 90 degrees. The corresponding simulation is carried out by using Matlab, which obtains the same results with the theoretical calculation. The results show that this method is feasible. Apart from these, this method is operated simply, of high measurement accuracy, and not leading to neutral overvoltage. This method can be used in the capacitive current measurement in the distribution network.
Key words:  distribution network  bias impedance method  phase angle difference  parameters to ground  measurement effect