引用本文:庄慧敏,巨辉,肖建.高渗透率逆变型分布式发电对 电力系统暂态稳定和电压稳定的影响[J].电力系统保护与控制,2014,42(17):84-89.
ZHUANG Hui-min,JU Hui,XIAO Jian.Impacts of inverter interfaced distributed generations with high penetration level on power system transient and voltage stability[J].Power System Protection and Control,2014,42(17):84-89
【打印本页】   【下载PDF全文】   查看/发表评论  【EndNote】   【RefMan】   【BibTex】
←前一篇|后一篇→ 过刊浏览    高级检索
本文已被:浏览 4865次   下载 4073 本文二维码信息
码上扫一扫!
分享到: 微信 更多
高渗透率逆变型分布式发电对 电力系统暂态稳定和电压稳定的影响
庄慧敏1, 巨辉1, 肖建2
1.成都信息工程学院控制工程学院,四川 成都 610225;2.西南交通大学电气工程学院,四川 成都 610031
摘要:
为研究大规模逆变型分布式发电对电力系统暂态和电压稳定性的影响,借助PSCAD/EMTDC仿真软件,以一个12母线测试系统为研究对象,建立电力系统和逆变型DG的动态模型。通过暂态仿真和理论分析,重点研究了不同渗透率DG对主同步发电机最大转速偏差和转速偏离频率的影响,分析了不同控制模式的DG在故障前(稳态)、故障期间和故障后对母线电压的影响。研究结果表明:渗透率越高,逆变型DG对系统暂态稳定性的负作用越大,但电压控制的逆变型DG能明显改善系统电压的稳定性。
关键词:  分布式发电  高渗透率  控制模式  动态模型  暂态稳定  电压稳定
DOI:
分类号:
基金项目:
Impacts of inverter interfaced distributed generations with high penetration level on power system transient and voltage stability
ZHUANG Hui-min1, JU Hui1, XIAO Jian2
1.School of Control Engineering, Chengdu University of Information Technology, Chengdu 610225, China;2.School of Electrical Engineering, Southwest Jiaotong University, Chengdu 610031, China
Abstract:
In order to investigate the impacts of large scale DGs on the power system transient and voltage stability, the dynamic models of the power system and DGs in a 12-bus test system are modeled in detail by PSCAD/EMTDC software. And then through simulation and theory analysis, the impact of the DGs with different penetration level on the maximum rotor speed deviation and the rotor speed deviation frequency of the main synchronous generators are studied, and the impact of the DGs with different control models on the power system bus voltages, before a fault (steady state), during a fault and after a fault is analyzed. The research results show that the inverter interfaced DGs have a more negative impact on the power system transient stability with the penetration level increasing, but the voltage controlled inverter interfaced DGs significantly improve the voltage in the power system buses after fault clearances.
Key words:  distributed generation  high penetration level  control mode  dynamic model  transient stability  voltage stability