引用本文: | 李卓昕,彭敏放,黄清秀,万 勋,刘 达.行波反射法在变压器绕组匝间短路故障定位中的应用[J].电力系统保护与控制,2016,44(21):84-89.[点击复制] |
LI Zhuoxin,PENG Minfang,HUANG Qingxiu,WAN Xun,LIU Da.Application of the traveling-wave reflection method in inter-turn short fault location for transformer[J].Power System Protection and Control,2016,44(21):84-89[点击复制] |
|
摘要: |
针对变压器绕组轻微匝间短路难以检测的问题,提出利用行波反射波的电压幅值进行匝间短路故障定位的方法。通过在变压器绕组线端输入单个低压脉冲以获取行波反射信号,从采集到的行波反射信号中提取相应的波峰电压幅值,以此作为故障诊断的电气量。根据匝间短路后对应匝波阻抗改变引起的反射电压突变,来实现匝间短路故障定位。仿真结果表明所提方法简单可行。 |
关键词: 变压器 行波反射法 波阻抗 匝间短路 故障定位 |
DOI:10.7667/PSPC151917 |
投稿时间:2015-10-30修订日期:2015-12-03 |
基金项目:国家自然科学基金项目(61173108;61472128)湖南省自然科学基金重点项目(14JJ2150) |
|
Application of the traveling-wave reflection method in inter-turn short fault location for transformer |
LI Zhuoxin,PENG Minfang,HUANG Qingxiu,WAN Xun,LIU Da |
(College of Electrical and Information Engineering, Hunan University, Changsha 410082, China ;College of Electrical and Information Engineering, Hunan University, Changsha 410082, China ;State Grid Hunan Electric Power Corporation Research Institute, Changsha 410007, China) |
Abstract: |
Aiming at the problem that the transformer winding is difficult to detect the fault of the inter-turn short circuit, the method of using the voltage amplitude of the traveling wave reflected wave to locate the fault location is proposed. It inputs a low voltage pulse into winding wire end to obtain the traveling wave reflection signal and extracts the traveling wave reflected signal from the peak voltage amplitude, which is used as the electric quantity of the fault diagnosis. According to the change of the reflected voltage caused by the turn to turn short circuit, the fault location of the inter-turn short circuit fault is realized. The simulation result shows that the proposed method is simple and feasible. This work is supported by National Natural Science Foundation of China (No. 61173108 and No. 61472128) and Natural Science Foundation of Hunan Province (No. 14JJ2150). |
Key words: transformer traveling wave reflection method wave impedance inter-turn short circuit fault location |