引用本文:张志强,余超耘,刘强,等.换流器保护在交流故障下的出口时序特性分析[J].电力系统保护与控制,2017,45(10):85-90.
ZHANG Zhiqiang,YU Chaoyun,LIU Qiang,et al.Research on the trip timing order characteristics of converter protections under AC faults[J].Power System Protection and Control,2017,45(10):85-90
【打印本页】   【下载PDF全文】   查看/发表评论  【EndNote】   【RefMan】   【BibTex】
←前一篇|后一篇→ 过刊浏览    高级检索
本文已被:浏览 4768次   下载 2078 本文二维码信息
码上扫一扫!
分享到: 微信 更多
换流器保护在交流故障下的出口时序特性分析
张志强1,余超耘2,刘 强1,蔡泽祥2
(1.广东省输变电工程公司,广东 广州 510160;2.华南理工大学电力学院,广东 广州 510640)
摘要:
当交流故障的故障条件不同时,换流器保护的出口结果和出口时间均具有不确定性,针对该问题展开系统的研究。梳理了换流器区故障和换流器保护的类型,并基于实际特高压直流工程的RTDS实验结果分析了交流故障下可能动作的换流器保护及其动作机理。详细分析了换流器保护的故障后电气特征离散性和计时原理,指出这是导致换流器保护动作时间不确定的两个原因。进一步深入对比了交流故障下存在出口时序离散性的3种换流器保护的动作逻辑,并结合上述特高压直流工程的RTDS实验结果分析了不同故障条件下这3种保护的出口时序特性。分析结果表明,这些保护延时定值极为接近,而且可能相互闭锁,不同故障条件下三者的出口时序关系决定了不同的动作结果。
关键词:  HVDC  交流故障  换流器保护  响应特性  出口时序
DOI:10.7667/PSPC160793
分类号:
基金项目:
Research on the trip timing order characteristics of converter protections under AC faults
ZHANG Zhiqiang1,YU Chaoyun2,LIU Qiang1,CAI Zexiang2
(1. Guangdong Province Transmission&Transformer Engineering Company, Guangzhou 510160, China;2. School of Electric Power, South China University of Technology, Guangzhou 510640, China)
Abstract:
This paper analyses the problem that the converter protections act uncertainly under different kinds of AC fault. Various internal faults and protections of converter zone are summarized, and the types of protection which can response to AC faults and the response mechanism are analyzed based on the RTDS experimental results of an actual UHVDC transmission system. This paper also analyses the uncertain electrical characteristics when faults occur as well as the timing principle of converter protections in detail, and points out that these are the two causes of the uncertain action of a converter protection. Further more, the logics of the protections whose trip order are uncertain under different faults are compared and the characteristics of their trip timing orders under different faults are analyzed based on the RTDS experimental results above. It reveals that the setting trip times of these protections are about the same, and one can probably be blocked by the others so that the trip timing orders under different faults determine the different action results.
Key words:  HVDC  AC fault  DC converter protection  response characteristics  trip timing order