引用本文: | 刘颖,戴栋,汪娟娟,等.基于逆变侧定电压控制的HVDC系统稳态和暂态响应特性研究[J].电力系统保护与控制,2017,45(24):1-8.[点击复制] |
LIU Ying,DAI Dong,WANG Juanjuan,et al.Transient and steady responses in HVDC system based on constant voltage control at inverter side[J].Power System Protection and Control,2017,45(24):1-8[点击复制] |
|
摘要: |
为测试逆变侧采用定电压控制和定关断角控制对直流输电系统稳态和暂态性能的影响,在CIGRE高压直流标准测试模型原有控制系统中增加了定电压控制模块,即整流侧采用定电流控制,逆变侧采用定电压、定电流和定关断角控制相互配合的控制方式。在PSCAD/EMTDC仿真平台中对其整流侧和逆变侧三相短路故障下的控制器特性进行了稳态及暂态仿真分析,并与相应的CIGRE标准模型暂态响应特性进行了对比。结果表明逆变侧增加定电压控制方式能够提高直流输电系统在交流故障扰动下的性能,减少换相失败的发生几率。 |
关键词: HVDC CIGRE高压直流标准测试模型 定电压控制 换相失败 暂态响应 |
DOI:10.7667/PSPC161985 |
投稿时间:2016-11-29修订日期:2017-01-03 |
基金项目:国家自然科学基金(51377061) |
|
Transient and steady responses in HVDC system based on constant voltage control at inverter side |
LIU Ying,DAI Dong,WANG Juanjuan,HAN Yongxia,LI Licheng,FU Chuang |
(School of Electric Power, South China University of Technology, Guangzhou 510641, China;Electric Power Research Institute, China Southern Power Grid Co., Ltd., Guangzhou 510080, China) |
Abstract: |
To test the effects of constant voltage control and constant extinction angle control on HVDC steady and transient performance, the control system of CIGRE HVDC benchmark model is complemented by a voltage control module, i. e. a constant current control is used at rectifier side, while a coordination control method combining voltage control, constant current control and constant extinction angle control is employed at inverter side. Steady and transient characteristics of the controller under three-phase short circuit fault at both rectifier and inverter sides are analyzed by using PSCAD/EMTDC simulations. The results show that, in comparison with CIGRE HVDC benchmark model, adding constant voltage control at inverter side could enhance the performance of HVDC system under the fault of AC side and lower the risk of commutation failure. This work is supported by National Natural Science Foundation of China (No.51377061). |
Key words: HVDC CIGRE HVDC benchmark model constant voltage control commutation failure transient response |