地区电网孤网运行事件的实例分析
黄淼1,文 旭2,刘育明3,文一宇3
(1.重庆邮电大学自动化学院,重庆 400065;2.国家电网公司西南分部,四川 成都 610041; 3.国网重庆市电力公司电力科学研究院,重庆 401123)
摘要:
为积累故障分析经验并给运行方式的制定提供参考,介绍并分析了一起实际的地区电网孤网运行事件。此事件源于一条220 kV输电线路的跳闸。该线路跳闸导致某地区电网形成孤网,进而发生机组甩负荷、低频减载、变电站母线过电压等行为。运用故障录波、仿真模拟和理论分析相结合的手段,明确了机组甩负荷等行为发生的原因,并探讨了维持孤网稳定运行的措施。理论探讨和仿真结果表明,对该起孤网运行事件的分析是正确有效的。
关键词:  故障分析  孤网  甩负荷  低频减载  过电压
DOI:10.7667/PSPC170983
分类号:
基金项目:重庆市教委科学技术研究项目资助(KJ1704101)
Case analysis for isolated operation of a regional power network
HUANG Miao1,WEN Xu2,LIU Yuming3,WEN Yiyu3
(1. College of Automation, Chongqing University of Posts and Telecommunications, Chongqing 400065, China;2. Southwest Subsection of State Grid Corporation of China, Chengdu 610041, China;3. State Grid Chongqing Electric Power Co. Electric Power Research Institute, Chongqing 401123, China)
Abstract:
In order to accumulate experience in fault analysis and provide a reference for the establishment of operating mode, this paper describes and analyzes an actual incident of isolated operation of a regional power network. This incident originated from a 220 kV transmission line trip, which led to the isolated operation of the regional power grid, followed by load rejection, under-frequency load shedding, substation overvoltage, etc. This paper uses fault wave recording, simulation and theoretical analysis to explore the causes of the above acts such as load rejection, and discusses the measures to maintain the stable running of grid. Theoretical discussion and simulation results show that the proposed analysis is effective and correct. This work is supported by the Science and Technology Research Program of Chongqing Municipal Education Commission (No. KJ1704101).
Key words:  fault analysis  isolated grid  load rejection  under-frequency load shedding  overvoltage