引用本文: | 王栋,高厚磊,李文琳,刘震.方向纵联保护对LCC-HVDC逆变侧交流线路的适应性分析[J].电力系统保护与控制,2018,46(18):33-40.[点击复制] |
WANG Dong,GAO Houlei,LI Wenlin,LIU Zhen.Adaptability analysis of directional pilot protection for AC transmission lines connected to LCC-HVDC inverter station[J].Power System Protection and Control,2018,46(18):33-40[点击复制] |
|
摘要: |
基于电压、电流故障分量的方向纵联保护原理广泛应用于交流线路的主保护。由于LCC-HVDC逆变侧交流线路具有不同于纯交流系统的故障特性,方向纵联保护能否继续适用需加以分析。首先,分析了逆变站三种不同的工作状态(未发生换相失败、发生单次换相失败、发生连续换相失败)对方向纵联保护的影响。其次,分析了逆变侧三种典型的交流出线结构(单回线单输电走廊、单回线多输电走廊、多回线输电走廊)对方向纵联保护的影响。最后,基于±800 kV天中直流系统(包括逆变侧500 kV交流出线)PSCAD仿真模型,验证了研究结论的正确性。 |
关键词: 方向纵联保护 LCC-HVDC 逆变侧交流线路 适应性 |
DOI:10.7667/PSPC201826 |
投稿时间:2018-01-15修订日期:2018-06-13 |
基金项目:国家重点研发计划资助项目(2016YFB0900603) |
|
Adaptability analysis of directional pilot protection for AC transmission lines connected to LCC-HVDC inverter station |
WANG Dong,GAO Houlei,LI Wenlin,LIU Zhen |
(Key Laboratory of Power System Intelligent Dispatch and Control of Ministry of Education, Shandong University, Jinan 250061, China) |
Abstract: |
Directional pilot protection principle, which is based on voltage and current fault components, is used in AC transmission lines widely. However, comparing to general AC transmission lines, the AC transmission lines which is connected to LCC-HVDC inverter station have different fault characteristic and the adaptability of directional pilot protection should be analyzed. Firstly, the effect of three different working status of inverter station (no commutation failure, single commutation failure or continuous commutation failure) on directional pilot protection is analyzed. Secondly, the effect of three different AC transmission line structures connected to inverter station (single transmission line, several single transmission lines or double transmission lines) on directional pilot protection is also analyzed. Eventually, ±800 kV Tian-Zhong LCC-HVDC transmission system (including 500 kV AC transmission system connected to inverter station) simulation model is established based on PSCAD and the simulation results prove the correctness of theoretical analysis. This work is supported by National Key Research and Development Program of China (No. 2016YFB0900603). |
Key words: directional pilot protection LCC-HVDC AC transmission line connected to inverter station adaptability |