引用本文: | 李 辉,田 野,陈江波,等.一二次融合成套断路器单相接地故障处置真型试验技术研究[J].电力系统保护与控制,2021,49(12):158-165.[点击复制] |
LI Hui,TIAN Ye,CHEN Jiangbo,et al.Research on a single-phase grounding fault handling true test of primary and secondary integration circuit breaker[J].Power System Protection and Control,2021,49(12):158-165[点击复制] |
|
本文已被:浏览 5848次 下载 1674次 |
码上扫一扫! |
一二次融合成套断路器单相接地故障处置真型试验技术研究 |
李辉1,2,田野3,陈江波1,2,邵苠峰1,2,万保权1,2,戴敏1,2,吴雪琼4,程婷4 |
|
(1.中国电力科学研究院有限公司,湖北 武汉 430074;2.电网环境保护国家重点实验室,湖北 武汉 430074;3.国网
辽宁省电力有限公司电力科学研究院,辽宁 沈阳 110000;4.国网电力科学研究院有限公司,江苏 南京 211000) |
|
摘要: |
目前一二次融合成套化柱上断路器的单相接地故障处置准确率低,亟需开展单相接地故障处置考核验证。在运行现场开展单相接地试验受制于安全风险和用户供电可靠性的影响,不易多次开展。通过建立10 kV真型配电网试验平台,实现了被试品快速接入,灵活复现配电网单相接地故障。提出了一二次融合成套柱上断路器单相接地故障处置真型试验方法,有效验证了一二次融合成套柱上断路器单相接地故障处置功能与处置准确率,发现了9项不合格原因。通过真型配电网试验平台的建立,提高了配电网设备入网质量,有效支撑配电网供电可靠性进一步提升。 |
关键词: 一二次融合 单相接地故障 故障处置 真型试验 |
DOI:DOI: 10.19783/j.cnki.pspc.200963 |
投稿时间:2020-08-08修订日期:2020-10-06 |
基金项目:国家电网公司科技项目资助“基于真型试验的配电自动化设备检测关键技术研究及应用”(5442PD210006,PD71-21-005) |
|
Research on a single-phase grounding fault handling true test of primary and secondary integration circuit breaker |
LI Hui1,2,TIAN Ye3,CHEN Jiangbo1,2,SHAO Minfeng1,2,WAN Baoquan1,2,DAI Min1,2,WU Xueqiong4,CHENG Ting4 |
(1. China Electric Power Research Institute Co., Ltd., Wuhan 430074, China; 2. State Key Laboratory of Power Grid
Environmental Protection, Wuhan 430074, China; 3. Electric Power Research Institute of State Grid Liaoning Electric Power
Co., Ltd., Shenyang 110000, China; 4. State Grid Electric Power Research Institute Co., Ltd., Nanjing 211000, China) |
Abstract: |
At present, the primary and secondary integration column circuit breaker single-phase ground fault disposal function and accuracy rate is lower. Thus it is urgent to carry out assessment and verification of single-phase ground fault disposal. A single-phase ground test at an operational site is subject to the safety risk and user power supply reliability. It is not easy to carry out frequently. In this paper, a 10 kV real distribution network test platform is built. The test object is quickly connected to the test position. The single-phase ground fault can be reproduced flexibly. A single-phase ground fault treatment true test method of a primary and secondary fusion complete column circuit breaker is put forward. The disposal function and accuracy rate of the primary and secondary fusion complete column circuit breaker are effectively verified. Nine unqualified problems are found in the test. Through the establishment of a real distribution network test platform, the quality of equipment is improved, and the reliability of the network power supply is further improved.
This work is supported by the Science and Technology Project of State Grid Corporation of China “Research and Application of Distribution Automation Equipment Detection Key Technology based on True Test” (No. 5442PD210006 and No. PD71-21-005). |
Key words: primary and secondary integration single-phase ground fault fault handling true test |