引用本文: | 林智勇,苏若杭,黄国泰,等.基于等值老化容抗的变压器油纸绝缘状态评[J].电力系统保护与控制,2025,53(03):140-147.[点击复制] |
LIN Zhiyong,SU Ruohang,HUANG Guotai,et al.Evaluation of the oil-paper insulation state of a transformer based on equivalent aging capacitance[J].Power System Protection and Control,2025,53(03):140-147[点击复制] |
|
本文已被:浏览 1525次 下载 255次 |
码上扫一扫! |
基于等值老化容抗的变压器油纸绝缘状态评 |
林智勇1,2,苏若杭1,2,黄国泰3,李荣华1,2,张达敏1,2 |
|
(1.厦门理工学院电气工程与自动化学院,福建 厦门 361024;2.厦门市高端电力装备及智能控制重点实验室,
福建 厦门 361024;3.福建省电力物资有限公司,福建 福州 350003) |
|
摘要: |
针对频域介电谱特征量难以定量分析变压器油纸绝缘老化状态的问题,提出应用等值老化容抗定量分析油纸绝缘老化状态的评估方法。首先,采用回复电压特征量构建变压器绝缘系统等效电路。然后,分析扩展德拜等效电路参数与频域介电谱的内在联系,研究时-频域介电谱相互转化的可行性。最后,通过仿真分析等效电路参数变化对复电容实部谱线的影响规律,定量分析等值老化容抗与主时间常数的关系。研究结果表明:等值老化容抗与主时间常数具有指数函数关系,当等值老化容抗越小时,变压器油纸绝缘老化越严重。由主时间常数与变压器绝缘老化状态关系可划分不同的变压器绝缘状态所对应的等值老化容抗范围,为准确评估变压器油纸绝缘老化状态提供新的参考依据。 |
关键词: 等效电路 频域介电谱法 主时间常数 等值老化容抗 |
DOI:10.19783/j.cnki.pspc.240632 |
投稿时间:2024-05-20修订日期:2024-10-07 |
基金项目:国家自然科学基金青年基金项目资助(51407151);福建省自然科学基金项目资助(2020J01281);福建省中青年教师教育科研项目资助(JZ230048) |
|
Evaluation of the oil-paper insulation state of a transformer based on equivalent aging capacitance |
LIN Zhiyong1,2,SU Ruohang1,2,HUANG Guotai3,LI Ronghua1,2,ZHANG Damin1,2 |
(1. School of Electrical Engineering and Automation, Xiamen University of Technology, Xiamen 361024, China;
2. Xiamen Key Laboratory of Frontier Electric Power Equipment and Intelligent Control, Xiamen 361024, China;
3. Fujian Electric Power Supplies Limited, Fuzhou 350003, China) |
Abstract: |
To address the difficulty in quantitatively analyzing the aging state of transformer oil-paper insulation using frequency domain spectroscopy characteristics, an evaluation method is proposed for analyzing the aging state of oil-paper insulation by equivalent aging capacitance. Firstly, the equivalent circuit of a transformer insulation system is constructed using recovery voltage characteristics. Then, the intrinsic relationship between the parameters of the extended Debye equivalent circuit and the frequency domain spectroscopy is analyzed, and the feasibility of time-frequency domain spectroscopy spectrum interconversion is studied. Finally, through simulation analysis, the influence of changes in equivalent circuit parameters on the real part of a complex capacitance spectrum is examined, and the relationship between equivalent aging capacitance and the main time constant is quantitatively analyzed. The results indicate that there is an exponential relationship between the equivalent aging capacitance and main time constant; the smaller the equivalent aging capacitance, the more severe the aging state of transformer oil-paper insulation. From the relationship between the main time constant and the aging state of the transformer oil-paper insulation, the equivalent aging capacitance range corresponding to different transformer insulation states can be determined, providing a new reference for accurately evaluating the aging state of transformer oil-paper insulation. |
Key words: equivalent circuit frequency domain spectroscopy principal time constant equivalent aging capacitance |