Analysis of single-phase grounding fault characteristics of low resistance grounding systemwith multi-distributed power supply
DOI:10.19783/j.cnki.pspc.231515
Key Words:distributed power system  single-phase grounding fault  distribution network through low resistance grounding mode  fault current  transformer grounding mode
Author NameAffiliation
TIAN Junyang1 1. Guangxi Power Grid Power Dispatching Control Center, Nanning 530023, China
2. College of New Energy, China University of Petroleum (East China), Qingdao 266580, China 
LI Haiyong1 1. Guangxi Power Grid Power Dispatching Control Center, Nanning 530023, China
2. College of New Energy, China University of Petroleum (East China), Qingdao 266580, China 
JIANG Liandian1 1. Guangxi Power Grid Power Dispatching Control Center, Nanning 530023, China
2. College of New Energy, China University of Petroleum (East China), Qingdao 266580, China 
SHEN Zizheng1 1. Guangxi Power Grid Power Dispatching Control Center, Nanning 530023, China
2. College of New Energy, China University of Petroleum (East China), Qingdao 266580, China 
REN Haolin2 1. Guangxi Power Grid Power Dispatching Control Center, Nanning 530023, China
2. College of New Energy, China University of Petroleum (East China), Qingdao 266580, China 
GUO Liwei2 1. Guangxi Power Grid Power Dispatching Control Center, Nanning 530023, China
2. College of New Energy, China University of Petroleum (East China), Qingdao 266580, China 
Hits: 3169
Download times: 379
Abstract:The single-phase grounding fault characteristics of the distribution network system via low resistance grounding mode will be affected by the grounding mode adopted by different types of grid-connected DGs. Aiming at the problem, combined with the symmetrical component method, a single-phase grounding fault analysis model of distribution network with multiple grid-connected DGs having different types and grounding modes is established first. The single-phase grounding fault point current of the system and the three-sequence current of the line are analyzed afterwards. Finally, the simulation model of single-phase ground fault is built by Matlab/Simulink, which verifies the correctness of the analysis of fault current characteristics. The results show that the grid-connected DG being ungrounded has the least impact on the system fault characteristics. This provides a theoretical basis for the selection of the type of grid-connected DG and the grounding mode of the grid-connected transformer.
View Full Text  View/Add Comment  Download reader