Adaptive impedance matching of medium voltage power line carrier communication based on PSA
DOI:10.19783/j.cnki.pspc.240437
Key Words:medium voltage power line communication  impedance matching  PSA  self-adaptation
Author NameAffiliation
XIE Zhiyuan School of Electrical and Electronic Engineering, North China Electric Power University, Baoding 071003, China 
CAO Tong School of Electrical and Electronic Engineering, North China Electric Power University, Baoding 071003, China 
Hits: 2719
Download times: 397
Abstract:In medium voltage power line communication, an adaptive impedance matching method for medium voltage power line carrier communication is proposed to solve the problem that line impedance mismatch caused by the variety and quantity of complex electrical components will influence the quality of communication. First, a model of a medium voltage impedance matching system is established, and a π-type adaptive impedance matching circuit is proposed based on the model. Then, an objective function conforming to the impedance conjugate matching principle is designed according to the circuit, and the optimal component parameters are found out by PID-based search algorithm (PSA) based on proportional integral differential (PID) to achieve the optimal objective function. Finally, based on this model, the advantages and disadvantages of PSA, particle swarm optimization (PSO) and genetic algorithms (GA) are simulated and analyzed. The results show that the PSA is superior to PSO and GA algorithms in terms of convergence speed and optimization accuracy, and can effectively realize impedance matching and improve carrier communication quality. This provides a feasible scheme for further research on medium voltage power line communication.
View Full Text  View/Add Comment  Download reader