Citation:Yan Huang,Hadi Nabipour Afrouzi,Hieng Tiong Su,et al.A Novel Test and Calibration Method for Digital Signals of Relay Protection Test Equipment for Intelligent Substation Based on FPGA[J].Protection and Control of Modern Power Systems,2026,V11(01):88-104[Copy]
Print       PDF       View/Add Comment      Download reader       Close
←Prev|Next→ Archive    Advanced Search
Click: 565   Download: 1220 本文二维码信息
A Novel Test and Calibration Method for Digital Signals of Relay Protection Test Equipment for Intelligent Substation Based on FPGA
Yan Huang,Hadi Nabipour Afrouzi,Hieng Tiong Su,Yuan Ping,Ismat Hijazin,Yangtao Xu,Ke Yan
Font:+|Default|-
Abstract:
With the widespread adoption of digital equipment in intelligent substations, testing digital signals in power systems has become an important role for relay protection test equipment. Testing and calibrating digital signals require high accuracy. However, existing methods have low precision, cannot be calibrated at full range for all indexes, and have complex configuration, making them unsuitable for routine calibration work. To solve the above problems, a novel calibration method is designed and implemented using field programmable gate array (FPGA) to achieve accurate input and output time control. Accurate calibration relies on multiple forms of traceability including theoretical value traceability based on waveform comparison, time scale value traceability based on accurate time stamps, and algorithm traceability based on typical algorithms. Compared with other existing methods, the proposed approach reduces the mean absolute error of action time and time measurement by 92.88%, effectively addressing a key industry challenge and offering a valuable reference for further research, application, and standardization.
Key words:  Relay protection test equipment, digital signal, calibration, field programmable gate array.
DOI:10.23919/PCMP.2024.000425
Fund:This work is supported by the Key Technologies R&D Program of Henan Province (No. 242102211065) and Postgraduate Education Reform and Quality Improvement Project of Henan Province (No. YJS2025GZZ36).