考虑机网协调的新型发电机失磁保护方案研究
陆秋瑜1, 徐飞1, 胡伟1, 张建坤1, 李淼2, 冯钢3
1.清华大学电机系电力系统国家重点实验室,北京 100084;2.湖北省电力公司调度通信中心,湖北 武汉 430077;3.内蒙古华电玫瑰营风力发电有限公司,内蒙古 呼和浩特 010000
摘要:
随着大型发电机组大量投运,失磁故障对系统的危害日益增大。在厂网分开的背景下,如何同时确保发电机和电网的安全稳定运行是一个值得关注的研究课题。针对发电机失磁保护在系统振荡时容易误动或拒动的问题,研究了失磁和振荡两种情况下系统电气量变化规律的不同特征,并结合不同失磁类型的特点,提出了电压、无功和时间三种新型判据,进而设计了计及机网协调的新型失磁保护方案,并给出了相应动作参数的整定方法。计算机仿真实验表明,新型方案可有效区分失磁和振荡现象,具有动作速度快、可靠性高的优点。
关键词:  失磁保护  系统振荡  电压判据  无功判据  时间判据  机网协调  计算机仿真
DOI:10.7667/j.issn.1674-3415.2013.09.001
分类号:
基金项目:国家高技术研究发展计划(863计划) (2012AA050207);国家科技支撑计划(2011BAA01B02);国家自然科学基金(51190101);国家电网公司科技项目;湖北省电力公司和国电南瑞科技股份有限公司科技项目
New loss of excitation protection scheme based on coordinated optimization between generator and grid
LU Qiu-yu,XU Fei,HU Wei,et al
Abstract:
As large capacity units is playing an increasily important role, loss of excitation failure has become more and more dangerous to the power system stability. Especially when the power plants and grid are seperated, it is a main concern to guarantee the security operation of both generators and grid. This paper concentrates on the mal-operation or misoperation problems of loss of excitation protection, which happen frequently in system swings. Based on the different generator performances in the two scenarioes and different kinds of loss of excitation failures, three innovative criterions including voltage, reactive power and timer criterions are proposed. Further, a new loss of excitation protection scheme based on the presented criterions is designed, and the scheme parameters tuning method is also introduced. The computer simulation results show that the new scheme can accurately distinguish the phenomena of loss of excitation from power system swings, and shows the advantages of high action speed and high reliability.
Key words:  loss of excitation protection  system swing  voltage criterion  reactive power criterion  timer criterion  coordinated optimization between generator and grid  computer simulation