引用本文:张巧霞,贾华伟,叶海明,等.智能变电站虚拟二次回路监视方案设计及应用[J].电力系统保护与控制,2015,43(10):123-128.
ZHANG Qiaoxia,JIA Huawei,YE Haiming,et al.Design and application of virtual secondary circuit monitoring in smart substation[J].Power System Protection and Control,2015,43(10):123-128
【打印本页】   【下载PDF全文】   查看/发表评论  【EndNote】   【RefMan】   【BibTex】
←前一篇|后一篇→ 过刊浏览    高级检索
本文已被:浏览 5725次   下载 3078 本文二维码信息
码上扫一扫!
分享到: 微信 更多
智能变电站虚拟二次回路监视方案设计及应用
张巧霞1, 贾华伟1, 叶海明2, 肖亮1, 李江林1, 张庭1, 张道农3
1.许继电气股份有限公司, 河南 许昌 461000;2.国网浙江省电力公司检修分公司, 浙江 杭州 311232;3.华北电力设计院工程有限公司,北京 100120
摘要:
针对智能变电站硬电缆回路被虚拟二次回路代替造成的信息不透明问题,提出了一种可视化的虚拟二次回路监视方案。该方案由过程层及间隔层设备判断虚拟二次回路异常并产生异常信号,利用一体化监控系统的数据传输通道,将虚拟二次回路异常信号以遥信的形式传输到站控层,站控层解析收到的异常信号并展示。在研究IEC 61850的短地址模型的基础上,利用短地址实现了站控层的遥信数据点与过程层及间隔层的虚拟二次回路异常信号之间的映射关系。根据现场使用情况,该方案解决了虚拟二次回路状态监视手段缺乏的问题,方便了问题的查找和定位,对运维人员来说是非常有用的。
关键词:  一体化监控系统  虚拟二次回路  虚拟二次回路监视  短地址  SCD
DOI:10.7667/j.issn.1674-3415.2015.10.020
分类号:
基金项目:
Design and application of virtual secondary circuit monitoring in smart substation
ZHANG Qiaoxia1, JIA Huawei1, YE Haiming2, XIAO Liang1, LI Jianglin1, ZHANG Ting1, ZHANG Daonong3
1.XJ Electric Co., Ltd., Xuchang 461000, China;2.Maintenance Branch, Zhejiang Electric Power Corporation, Hangzhou 311232, China;3.North China Power Engineering Co., Ltd., Beijing 100120, China
Abstract:
Aiming at the information opaque problem that caused by hard cable loops are replaced by virtual secondary circuit in smart substation, a solution of visualized circuit monitoring is proposed, which uses the IEDs in process layer and bay layer to determine whether a virtual secondary circuit is abnormal and generating abnormal signals, then the signals are sent to station layer by data transmission channel of the integrated supervision and control systems in the form of telesignalling, finally, the abnormal signals are received and analyzed and displayed by the station layer. Based on the research of IEC61850’s short address model, it establishes the mapping between telesignalling in station layer and virtual secondary circuit abnormal signals in process layer and the bay layer by short address. According to the usage in smart substation, the solution is very helpful to operation and maintenance personnel, it solves the lack of means for monitoring on virtual secondary circuit state, and is convenient to find and locate the problem.
Key words:  integrated supervision and control systems  virtual secondary circuit  virtual secondary circuit monitoring  short address  SCD