引用本文: | 裘愉涛,潘武略,倪传坤,何荷,文明浩.风电场送出线等传变距离保护[J].电力系统保护与控制,2015,43(12):61-66.[点击复制] |
QIU Yutao,PAN Wulüe,NI Chuankun,HE He,WEN Minghao.Equal transfer process-based distance protection for wind farm outgoing transmission line[J].Power System Protection and Control,2015,43(12):61-66[点击复制] |
|
摘要: |
分析了具备低电压穿越(LVRT)能力的双馈式风电场送出线路故障暂态特性。风电送出线路风场侧保护测得的电压与电流主要频率分量不一致,致使传统的依据工频电压、电流相量的距离保护元件动作性能受到严重影响,无法正常工作。基于输电线路时域模型的解微分方程算法不涉及信号的频域信息,可以克服送出线电压、电流主频不同带来的影响,但受高频分量的影响较大。等传变距离保护相较传统的解微分方程算法,增加了低通滤波及故障点电压重构两个环节,显著改善了算法的测距性能。PSCAD/EMTDC仿真结果表明,线路不同位置处发生不同类型故障时,等传变距离保护算法均可以实现快速、准确测距。 |
关键词: 风电场 双馈感应发电机 送出线 解微分方程算法 等传变距离保护 |
DOI:10.7667/j.issn.1674-3415.2015.12.010 |
投稿时间:2014-09-22修订日期:2014-11-26 |
基金项目:国家自然科学基金资助项目(51477061,51077061) |
|
Equal transfer process-based distance protection for wind farm outgoing transmission line |
QIU Yutao,PAN Wulüe,NI Chuankun,HE He,WEN Minghao |
(Zhejiang Electric Power Company, Hangzhou 310007, China;XJ Electric Co., Ltd., Xuchang 461000, China;State Key Laboratory of Advanced Electromagnetic Engineering and Technology
(Huazhong University of Science and Technology), Wuhan 430074, China) |
Abstract: |
The fault features of outgoing transmission line in DFIG-based wind plant with the capacity of low-voltage ride-through (LVRT) are analyzed. The main frequency inconsistency between voltage and current of wind farm outgoing transmission line leads a serious impact on the action performance of traditional distance protection element based on power frequency voltage and current phasor. The differential equation algorithm based on the time-domain differential equation model of transmission line does not involve the frequency-domain information of the signal, thus it is unaffected by the main frequency inconsistency between voltage and current of wind farm outgoing transmission line. But the high-frequency characteristic of the differential equation algorithm is poor. Compared with the traditional differential equation algorithm, two processes are gained in the equal transfer process-based distance protection, low-pass filtering and re-structuring of the voltage at the fault point, which significantly improves the performance of the algorithm. The PSCAD/EMTDC simulation results show that the distance element which employs the equal transfer process-based distance protection algorithm can trip correctly and quickly while unaffected by the wind power transient voltage and current no matter what kind of fault occurs in the protection scope. |
Key words: wind plant doubly fed induction generator (DFIG) outgoing transmission line differential equation algorithm equal transfer process-based distance protection |