引用本文: | 张太升,韩 伟,杨 霖,等.基于波形相关分析的双馈风电场送出线时域距离保护[J].电力系统保护与控制,2021,49(14):82-88.[点击复制] |
ZHANG Taisheng,HAN Wei,YANG Lin,et al.Time-domain distance protection for transmission lines of doubly-fed wind farms based on waveform correlation analysis[J].Power System Protection and Control,2021,49(14):82-88[点击复制] |
|
本文已被:浏览 4960次 下载 1440次 |
码上扫一扫! |
基于波形相关分析的双馈风电场送出线时域距离保护 |
张太升1,2,韩伟3,杨霖4,田宝江1,陈玉4,段文岩3,姚孟1,文明浩4 |
|
(1.国网河南省电力公司电力调度控制中心,河南 郑州 450052;2.国网河南省电力公司焦作供电公司,
河南 焦作 454003;3.国网河南省电力公司电力科学研究院,河南 郑州450052;
4.强电磁工程与新技术国家重点实验室(华中科技大学),湖北 武汉 430074) |
|
摘要: |
双馈风机故障暂态特性与传统同步发电机不同,其短路电流成分复杂,导致基于工频相量的距离元件动作性能劣化。为了解决工频相量距离保护在双馈风电场送出线中应用时存在的问题,提出了一种基于波形相关分析的时域距离保护方案。分析了波形相似度的原理及时间窗选取的依据,通过仿真验证了所选时间窗的合理性。基于此分析,构造了时域距离保护判据,并在PSCAD/EMTDC仿真平台上搭建模型进行了测试。仿真结果表明,在不同故障类型下,所提出的时域距离保护基本不受双馈风机故障特性的影响,具有较好的动作性能。 |
关键词: 双馈风机 波形相似度 工频相量距离保护 时域距离保护 Prony算法 |
DOI:DOI: 10.19783/j.cnki.pspc.201284 |
投稿时间:2020-10-26修订日期:2021-01-07 |
基金项目:国家自然科学基金项目资助(51877090) |
|
Time-domain distance protection for transmission lines of doubly-fed wind farms based on waveform correlation analysis |
ZHANG Taisheng1,2,HAN Wei3,YANG Lin4,TIAN Baojiang1,CHEN Yu4,DUAN Wenyan3,YAO Meng1,WEN Minghao4 |
(1. State Grid Henan Electric Power Dispatching Control Center, Zhengzhou 450052, China; 2. Jiaozuo Power Supply
Company, State Grid Henan Electric Power Company, Jiaozuo 454003, China; 3. State Grid Henan Electric Power
Research Institute, Zhengzhou 450052, China; 4. State Key Laboratory of Advanced Electromagnetic Engineering
and Technology, Huazhong University of Science and Technology, Wuhan 430074, China) |
Abstract: |
The fault transient characteristics of a Doubly Fed Induction Generator (DFIG) are different from traditional synchronous generators. The short-circuit current components of the former are complex. They may lead to the deterioration of the operating performance of the distance protection based on the power frequency phasor. To solve the problems of power frequency phasor based distance protection being applied in the transmission lines of double-fed wind farms, a time-domain distance protection based on waveform correlation analysis is proposed. The principle of waveform similarity and the standard of time window selection are analyzed. The rationality of the selected time window is verified by simulation. Then, the time-domain distance protection criterion is constructed. A simulation model is built and tested using the PSCAD/EMTDC platform. The simulation results show that the proposed time-domain distance protection is basically unaffected by DFIG fault characteristics and has good performance under different types of faults.
This work is supported by the National Natural Science Foundation of China (No. 51877090). |
Key words: doubly fed induction generator waveform similarity power frequency phasor based distance protection time-domain distance protection Prony method |