Abstract: |
The active saturated iron-core superconductive fault current limiter (SISFCL) is a good choice to decrease fault
current. This paper introduced the principles and impedance characteristic of the active SISFCL. Then, it shows the
current-limiting effects of the SISFCL. Besides, the impact of the active SISFCL on the distance protection of the EHV
transmission line is evaluated. Based on that, the coordination scheme of the distance protections is proposed. A
500 kV double-circuit transmission system with SISFCLs is simulated by Electro-Magnetic Transients Program including
DC (EMTDC). Simulation tests demonstrate the correctness and validity of theoretical analyses. |
Key words: Superconductive Fault current limiter (SFCL), Saturated iron core, Distance protection, Current-limiting effects |