• Home
  • Information
  • Editorial Board
  • Submission Guidelines
  • Template for PCMP
  • Ethics & Disclosures
Citation:Amir Ghorbani,Seyed Yaser Ebrahimi,Morteza Ghorbani.Active power based distance protectionscheme in the presence of seriescompensators[J].Protection and Control of Modern Power Systems,2017,V2(1):57-69[Copy]
Print       PDF       View/Add Comment      Download reader       Close
←Prev|Next→ Archive    Advanced Search
Click: 1695   Download: 882 本文二维码信息
Active power based distance protectionscheme in the presence of seriescompensators
Amir Ghorbani,Seyed Yaser Ebrahimi,Morteza Ghorbani
Font:+|Default|-
Abstract:
Flexible ac transmission system (FACTS) controllers, especially the series-FACTS controllers, affect the operation of distance relays and can lead to the relays under/over-reaching. This paper aims to demonstrate the effects of static synchronous series compensator (SSSC) and series capacitive compensation (SCC), as two important series compensators, on the distance protection using theoretical and computational methods. The results of the investigation are used to develop a feasible and adequate method for eliminating the negative effects of these devices on the distance relays. The developed method measures the voltages at terminals of the SSSC and SCC by phasor measurement units (PMUs) which are then transmitted to the relay location by communication channels. The transmitted signals are used to modify the voltage measured by the relay. Different operation types and conditions of SSSC and SCC, and different faults such as phase-to-phase and phase-to-ground faults are investigated in simulations. Since the modeled distance relay can measure the fault resistance, trip boundaries are used to show the performance of the presented method. Results show that the presented method properly eliminates the negative effects on the distance relays and prevents them from mal-operation under all fault resistance conditions.
Key words:  Isolated community microgrid, Temperature controlling devices, Economic operation, Energystorage system
DOI:10.1186/s41601-017-0034-4
Fund:
Protection and Control of Modern Power Systems
Add: No. 17 Shangde Road, Xuchang 461000, Henan Province, P. R. China
E-mail: pcmp@vip.126.com     Tel: 0374-3212254/2234
  copyright Power Kingdom 2022.豫ICP备17035427号-1