Citation:Balimidi Mallikarjuna,Pudi Shanmukesh,Dwivedi Anmol,Maddikara Jaya Bharata Reddy,Dusmanta Kumar Mohanta.PMU based adaptive zone settingsof distance relays for protection ofmulti-terminal transmission lines[J].Protection and Control of Modern Power Systems,2018,V3(2):126-140[Copy] |
|
Abstract: |
This paper proposes Phasor Measurement Unit (PMU) based adaptive zone settings of distance relays (PAZSD)
methodology for protection of multi-terminal transmission lines (MTL). The PAZSD methodology employs current
coefficients to adjust the zone settings of the relays during infeed situation. These coefficients are calculated in
phasor data concentrator (PDC) at system protection center (SPC) using the current phasors obtained from PMUs.
The functioning of the distance relays during infeed condition with and without the proposed methodology has
been illustrated through a four-bus model implemented in PSCAD/EMTDC environment. Further, the performance
of the proposed methodology has been validated in real-time, on a laboratory prototype of Extra High Voltage
multi-terminal transmission lines (EHV MTL). The phasors are estimated in PMUs using NI cRIO-9063 chassis
embedded with data acquisition sensors in conjunction with LabVIEW software. The simulation and hardware
results prove the efficacy of the proposed methodology in enhancing the performance and reliability of
conventional distance protection system in real-time EHV MTLs. |
Key words: Extra high voltage (EHV), Multiterminal transmission line (MTL), Phasor measurement unit (PMU),Phasor data concentrator (PDC), Current coefficients |