• Home
  • Information
  • Editorial Board
  • Submission Guidelines
  • Template for PCMP
  • Ethics & Disclosures
Citation:Yude Yang,Anjun Song,Hui Liu,等.Parallel computing of multi-contingencyoptimal power flow with transient stabilityconstraints[J].Protection and Control of Modern Power Systems,2018,V3(2):204-213[Copy]
Print       PDF       View/Add Comment      Download reader       Close
←Prev|Next→ Archive    Advanced Search
Click: 1571   Download: 983 本文二维码信息
Parallel computing of multi-contingencyoptimal power flow with transient stabilityconstraints
Yude Yang,Anjun Song,Hui Liu,Zhijun Qin,Jun Deng,Junjian Qi
Font:+|Default|-
Abstract:
To deal with the high dimensionality and computational density of the Optimal Power Flow model with Transient Stability Constraints (OTS), a credible criterion to determine transient stability is proposed based on swing curves of generator rotor and the characteristics of transient stability. With this method, the swing curves of all generator rotors will be independent one another. Therefore, when a parallel computing approach based on the MATLAB parallel toolbox is used to handle multi-contingency cases, the calculation speed is improved significantly. Finally, numerical simulations on three test systems including the NE-39 system, the IEEE 300-bus system, and 703-bus systems, show the effectiveness of the proposed method in reducing the computing time of OTS calculation.
Key words:  Power system, Transient stability, Multi-contingency, Optimal power flow, Parallel computing
DOI:10.1186/s41601-018-0095-z
Fund:
Protection and Control of Modern Power Systems
Add: No. 17 Shangde Road, Xuchang 461000, Henan Province, P. R. China
E-mail: pcmp@vip.126.com     Tel: 0374-3212254/2234
  copyright Power Kingdom 2022.豫ICP备17035427号-1