Citation:Swagata Das,Sundaravaradan Navalpakkam Ananthan,Surya Santoso.Estimating zero-sequence impedance ofthree-terminal transmission line and Theveninimpedance using relay measurement data[J].Protection and Control of Modern Power Systems,2018,V3(4):373-382[Copy]
Print       PDF       View/Add Comment      Download reader       Close
←Prev|Next→ Archive    Advanced Search
Click: 1398   Download: 926 本文二维码信息
Estimating zero-sequence impedance ofthree-terminal transmission line and Theveninimpedance using relay measurement data
Swagata Das,Sundaravaradan Navalpakkam Ananthan,Surya Santoso
Font:+|Default|-
Abstract:
Current and voltage waveforms recorded by intelligent electronic devices (IEDs) are more useful than just performing post-fault analysis. The objective of this paper is to present techniques to estimate the zero-sequence line impedance of all sections of a three-terminal line and the Thevenin equivalent impedance of the transmission network upstream from the monitoring location using protective relay data collected during short-circuit ground fault events. Protective relaying data from all three terminals may not be always available. Furthermore, the data from each terminal may be unsynchronized and collected at different sampling rates with dissimilar fault time instants. Hence, this paper presents approaches which use unsynchronized measurement data from all the terminals as well as data from only two terminals to estimate the zero-sequence line impedance of all the sections of a three-terminal line. An algorithm to calculate positive-, negative- and zero-sequence Thevenin impedance of the upstream transmission network has also been presented in this paper. The efficacy of the proposed algorithms are demonstrated using a test case. The magnitude error percentage in determining the zero-sequence impedance was less than 1% in the test case presented.
Key words:  Zero-sequence, Three-terminal line, Thevenin Impedance
DOI:10.1186/s41601-018-0108-y
Fund:
Protection and Control of Modern Power Systems